|
Q: Regarding 1.3 Special Technical Requirements for
all use groups (except R3/R4), what about pressure criteria and pump requirements?
At this point your concern would be only the designated
work area. Assuming you were working below the 8th floor you would size
the riser for the entire building then deal with fire pump if and when
you rehab the 8th floor.
Q: If I have a sprinklered building, which by todays
NCSBC does not require it to be sprinklered, and I am gutting the building,
can the sprinkler system be removed?
According to Sec. 1.4c (2) Existing fire alarm, fire
suppression and standpipe systems shall not be removed without replacement
and shall be maintained in operating condition.
Q: What if the existing head layout doesnt
conform?
In this case you would modify the head layout to fit
the alteration or reconstruction proposed.
Q: What happens when flow control devices installed
during an alteration negatively impact the sprinkler system flow rate?
When you alter a system you must do it as required
by the code. However, modifications cannot degrade the existing sprinkler
system.
Q: In supplemental requirements (Sec. 1.11A) would
there be a requirement for fire barrier separation between sprinklered
work area and unsprinklered work areas?
No
Q: What about an unenclosed existing stairway?
Sec. 1.1 g 4iii Introduction states in regards to change
of use hazard indexes: Stairways and other vertical openings located
in a building or portion of a building where there is a change of use
are required to meet certain enclosure requirement for the new use which
are specified in Sections 1.12 through 1.28 of the NCRC.
Q: Do you need to rate a structure/space because
of change of use?
Only if it is required as part of a one hour space
separation.
top
Back
to previous page
|